Three stage Detection verification process to pinpoint fire location Detection And Suppression in the
Horizontal and Vertical Plane Can be mounted upright or inverted
The Detection And Suppression System has a Range of 60 Feet Rotating 360 degrees The System
Detectors Senses Radiant Energy
The System uses 6 Multi-Spectrum Digital Electro-optical Flame Detectors
Horizontal Plane 3 Detectors 120 degrees cone of vision
Vertical Plane 3 Detectors 120 degrees cone of vision
Sensitivity 60 ft to a 1 sq ft heptane fire Operating Temperature -40° to 185°F (-40° to 85°C) Wide
field of view and solar blind Spectral Sensitivity
Ultraviolet: 185 to 260 nanometers Wide Band Infrared: 0.7 to 3.5 micrometers Visible: 400 to 700
nanometers
The System Will Detect Hydrocarbon And Non-Hydrocarbon Fires Radiant energy from all types of
flaming fires will alert the Detection And Suppression System Looking in The Ultraviolet Visible and
Infrared Spectrum